Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> Power Supply, Inverter & Solar---Page2 >> EPS Series
   

EPS Series

 
 
 
1.Usage
 
Emergency power supplied to the equipment of 380V/220V, such as fire protection facility or direct load or especially important load or fire protection emergency light load or other loads Installation form: On the ground (standard power cupboard) Backup time: 90-120 minuted, (standard), the backup time coule be deposited as designed Specification: 2KW-800KW Specification: 2,4,6,8,10,15,20,25,30,45,55,75,95,110,130,160,180,200,220,250,280,315,400, 500,630,800KW. These products are used for force load and fire protection emergency light.
 
 
2.Product summary
 
EPS Series is of high technical green product with CPU controlled, digital circuit and high integrated level electronic element, which adopts module inverter produced by international famous manufactory, and the newest fifth IGBT and invert technique.This product provieds the second or third powr for the direct load and especially important load facility and fire protection equipment or light.
 
 
3.Product summary
 
Static, no noise, no arranged cigarettes, no common damage, no fire hidden danger Switch over automatically without people Save energy, lose little power without emergency power supplied Stable capability,reliable safety and long using life Comparing with generator, it’s comprehensive price is lower and capability price ratio is better.
 
 
4.Characteristics
 
Adopt the newest IGBT invert module and high reliable integrated circuit Modulate PWM technology in pulse width, four in one desigmm,constructer simplified Supply power to any inductive or capacityve loads Link with fire control, could realize building intelligent monitor by distance and fire protection All the main componets adopt the high reliable well-known brand Direction wires and parts are of fire-netardant and un-burnt characteristics.
Notice:
1. EPS series is used for three phases, single phase or mixed type electrical equipment, such as lift, water pump, air blower, light, the screen of securities, air conditioner, office equipment, finacial institution and so on.
2.Auto. fire protection linking device could be chosen.
3. When the EPS needs fire protection link, remote monitor and output with multi-loops, please make sure before making order.
 
 
5.EPS products tecnincal parameter
 
Type EPS-800KW
Voltage
380±20%
Input
Phase
Three phases four wires+PE
Frequency
50HZ±5%
Capacity
2KW-800KW
Output
Voltage
380VAC Three phases four wires+PE
Voltage Precision
±5%
Waveform
Sine wave distortion ≤ 3%
Frequency
50HZ±0.5%
Overload capacity
120% ordinarily run
Regulating time
<0.2s
Battery
Sealed battery maintained for free
Backup time
Standard time is 90 minuted or 120 minuted (backup time could be deposited as required)
Protection
Short-circuit protection, over-current protection, could run lack of phase
Display
LED or LCD
Efficiency
Power supplied emergently:above90%, Power supplied by electric net:about 100%
Operation environment
Temperature:-24oC-40oC, Relative humidity: 0-90% sealever height:less than 2000m
Noise
When there is city power, placed without noise, otherwise, the noise<55dB, larger than EPS-75KW, the noise<65dB
Size/weight
See the size and weight list
The method of door-opened and wires entry
The front door single open, the back door double open, the wires enter from the bottom(standard type)
 
Notice:
1.The output loop could be made inside the cupboard as required.
2.Detail specification: 2,4,6,8,10,15,20,25,30,35,55,75,95110,130,160,180,200,280,315,400,500,630,800KW.
 
 

 

 

  Back